Alongside increased winding and oil temperatures, the moisture content in the oil is one of the most critical factors that can massively shorten the service life of a transformer, since both temperature and moisture can damage the paper insulation and therefore also have a negative effect on the thermal insulating properties.
A Chinese steel works experienced this first hand at the end of 2018, when moisture levels triggered early warnings. Thanks to the MR EXPIOTECH MMS Moisture Management System, they were able to reduce the moisture content and prevent their transformers from failing prematurely.
The steel works had operated three 22,000 kVA/35 kV furnace transformers for more than five years. However, since commissioning, the three transformers had not undergone regular maintenance or diagnostic measurements. In the fall of 2018, oil analyses were finally carried out, the results of which showed that the moisture and acetylene contents in the oil of all three power transformers significantly exceeded the relevant standards. This caused their dielectric strength to drop, which triggered the aforementioned early warning signals on two of the transformers.
Those in charge therefore decided upon comprehensive maintenance for these two transformers, during which one transformer would be shut off while the other two continued to keep operations running. During maintenance, the service technicians determined, among other things, that a lot of water had collected on the bottom of the transformer tank, that the iron core was accordingly rusty, and that the insulation resistance to ground was too low. The two transformers suffered from different levels of damage, which could be traced back to the irregular performance of maintenance and diagnostics.
The steel works operator decided to take measures to combat this in advance before the third transformer also triggered an early warning. To reduce the moisture content effectively and thus avoid damage to the transformer, it is important to determine and reduce the moisture not just in the oil, but also in the insulating paper. Due to the dynamic equilibrium and the unequal distribution of moisture content, this requires a special drying method. For this purpose, the operator chose innovative MR technology. The new MR EXPIOTECH Moisture Management System was put to use for the first time in China, removing 4.3 L of water from the paper over an extended period during continuing operation.
Source: MR